What is Return Air? An air handling unit that supplies air in a building requires a continuous replenishment of air to supply. For example, a residential oscillating fan has two sides: a discharge or high-pressure side and a suction or low-pressure side and the air discharged from it is equal to the air supplied to it. A building air handling unit must be in equilibrium, so, the volume of air that is supplied from it must equal the volume of air returned to it. For example, if 100% outside air is brought into the building, the same volume of air will be discharged from the building to replenish that from outside and keep the air system in equilibrium. In a building when there is concern for the possibility of contaminated air returning to an air handling unit (called the return-air), the air will usually return through ducts (return-air ducts). Hospitals are good examples of buildings where some or all return air may be ducted. In many other types of buildings, air that must return to air handling units is often not ducted. Instead, air makes its way back to the units by a pressure differential created on the suction side of the fans in the air handling units that causes the supplied air to return back to the units. A common route for air to return to an air handling unit is via the ceiling space, which becomes one large duct called a return air space or return air plenum. The use of a ceiling space as a return air plenum has important considerations in building construction. The discussion above about air movement shows that any smoke in the return air plenum would be drawn towards the air handling unit. If an air handling system is one that recirculates most of the air, smoke could be drawn through the air handling unit and be widely distributed in the building via supply air ducting. For this reason, building codes dictate that materials for use in air plenums must show minimal ability to support combustion in case there were a fire in the plenum. As well, materials in the plenum must contribute minimally, if at all to fire and smoke production. To ensure this minimal fire and smoke contribution, there are tests performed by various laboratories that assess suitability for installation of building components in air plenums. For example, some electrical cables are acceptable for installation in plenums and such ratings relate to the composition of the outer jacket material, which is different from the jacket on cables that do not have a plenum rating. Plenum-rated cables are more expensive than non-plenum rated cables.
Leon P. Gander’s Post
More Relevant Posts
-
Avoid Roof Leakage After a Solar installation on the Roof Have you been in a situation where, after a solar installation on your roof, it begins to leak? Yes, it could happen to the best of us if proper care is not taken. 1. Please, access that roof you want to climb. Get a carpenter to assess the roof before work begins. The carpenter checks the state of the rooftop to confirm if it can hold the weight of the panels or if it needs repair. If you don't have a carpenter, you can do this yourself. Just check for weak spots, rust, or signs of wear and tear. . 2. Use Sealant or Roof Gum Even if there's no visible damage, apply sealant—what we call "roof gum" —where you plan to drill screws into the roof. This precaution helps to create a waterproof barrier at the points where the roof is penetrated. Just go to those selling building materials and ask for roof gum. They would supply to you. It’s not expensive at all. . 3. Walk Carefully on the Roof Abeg, If the roof is old, especially in villages, avoid walking directly on the roof surface to prevent damage. It's best to walk on the "gutter part" of the roof or use a plank to spread your weight. So you would not create dents or cracks that will cause leaks once the solar panels are installed. . 4. Avoid Creating "Potholes" on the Roof When installing, take care not to create any dents that could stop the roof’s water drainage system. Imagine when rain falls and water settles in the middle of the roof due to a dent—this can lead to leaks. Please, make sure there’s a clear path for water to flow off the roof. . 5. Use Rails for Large Installations For larger installations, don't place the panels directly on the roof. Use rails to create some space between the roof and the panels, allowing for proper airflow and preventing heat buildup or further stress on the roof. Thanks for reading, and continue learning and improving.
To view or add a comment, sign in
-
-
Good #insulation has become a critical #component to improving the effectiveness of #steel #buildings and providing ideal comfort. We believe in the value of incorporating insulated metal panels early into the design of projects. Insulation enhances energy efficiency, temperature control and overall performance of any finished structure. It also offers our clients even greater value by reducing long-term #energy #costs and improving comfort. Proper insulation keeps a structure warmer in the winter and cooler in the summer so that operations rely less on mechanical heating and air conditioning systems and #HVAC usage. Read about the different insulation systems we use and why insulated metal panels (IMPs) are so important for smart #building systems. #engineering #business #management #operations #maintenance BOMA Canada Canadian Manufacturers & Exporters Trade & Invest British Columbia Greater Vancouver Board of Trade Canadian Federation of Independent Business BC Agriculture Council BC Chamber of Commerce Ontario Chamber of Commerce #realestate
To view or add a comment, sign in
-
"Soundproof PPRC pipes" likely refers to PPRC (Polypropylene Random Copolymer) pipes that are designed to reduce noise transmission compared to standard pipes. Here are some features and characteristics that may be associated with soundproof PPRC pipes: Special Construction: Soundproof PPRC pipes may have a unique construction or additional layers designed to dampen sound vibrations and reduce noise transmission through the pipe walls. Acoustic Insulation: These pipes may incorporate materials with acoustic insulation properties, such as foams or sound-absorbing layers, to minimize noise propagation within the piping system. Noise Reduction: Soundproof PPRC pipes are engineered to attenuate the transmission of noise generated by flowing fluids, such as water or air, as they pass through the piping system. This can help maintain a quieter environment in residential, commercial, or industrial settings. Applications: Soundproof PPRC pipes are commonly used in buildings where noise reduction is a priority, such as residential apartments, hotels, hospitals, schools, or office buildings. They are particularly beneficial in applications where plumbing systems are located near sensitive areas or where noise disturbance is a concern. Compatibility: Despite their soundproofing features, these pipes maintain the same compatibility and performance characteristics as standard PPRC pipes. They are suitable for use in plumbing, HVAC (heating, ventilation, and air conditioning), and other fluid transportation systems. It's important to note that the effectiveness of soundproof PPRC pipes may vary depending on factors such as pipe diameter, wall thickness, installation method, and surrounding environmental conditions. Additionally, consulting with manufacturers or suppliers specializing in soundproof piping solutions can provide more detailed information on the specific features and performance of these pipes.
To view or add a comment, sign in
-
Bitumen Roll Roofing Roof insulation is a crucial phase in both construction and maintenance, as it protects buildings from water leaks, reduces operational costs, and extends the building's lifespan. Among the most commonly used materials for roof insulation is bitumen rolls. In this article, we will delve into the nature of bitumen rolls, their installation method, advantages, disadvantages, and the overall importance of roof insulation. What are #Bitumen Rolls? Bitumen rolls are flexible insulating materials made from modified bitumen, a black, viscous substance derived from crude #oil. Bitumen rolls are characterized by their high flexibility and ability to adapt to temperature changes, making them ideal for roof insulation. Bitumen rolls consist of several layers, including a base layer of polyester or fiberglass, a middle layer of modified bitumen, and a protective top layer. Installation of Bitumen Rolls The installation process of bitumen rolls involves several stages: Preparation: The surface is thoroughly cleaned of dirt, dust, and grease, and any cracks or holes are repaired. Primer: A primer layer is applied to enhance the adhesion of the bitumen rolls to the surface. Installation: Bitumen rolls are unrolled onto the surface gradually, ensuring an overlap between the rolls, and the rolls are welded together using a gas torch. Protection: A protective layer of gravel or sand is applied over the bitumen rolls to shield them from sunlight and mechanical damage. Advantages of Bitumen Rolls High flexibility: Bitumen rolls can withstand movement and expansion caused by temperature changes. Water resistance: Bitumen rolls protect the building from water leaks. Long lifespan: Bitumen rolls have a long lifespan of 20 years or more. Easy installation: Bitumen rolls can be installed quickly and easily. Affordable: Bitumen rolls are considered economical insulating materials. Disadvantages of Bitumen Rolls Affected by extreme heat: Bitumen rolls may be damaged by extremely high temperatures. Requires skilled installation: Bitumen rolls should be installed by specialized technicians. Not resistant to severe mechanical damage: Bitumen rolls may be damaged by severe mechanical impacts. Importance of Roof Insulation Leakage protection: Roof insulation protects the building from water leaks that can lead to moisture and damage to the building. Thermal insulation: Roof insulation reduces heat transfer from the outside to the inside and vice versa, saving on air conditioning and heating costs. Sound insulation: Roof insulation reduces the transmission of sound from the outside to the inside and vice versa, providing a quieter environment. Protection of the building from weather elements: Roof insulation protects the building from various weather elements such as rain and ultraviolet rays. Increased building lifespan: #Roof #insulation extends the #building's lifespan and maintains its value. #ayloulconstructions #waterproof #constructions #engineer
To view or add a comment, sign in
-
🚀 𝗛𝗩𝗔𝗖 𝗳𝗼𝗿 𝗢𝗶𝗹 & 𝗚𝗮𝘀 𝗙𝗮𝗰𝗶𝗹𝗶𝘁𝗶𝗲𝘀 ( 𝗦𝗲𝗿𝗶𝗲𝘀- 𝟱𝟳 | 𝗣𝗮𝗿𝘁 𝟭𝟲 𝗼𝗳 𝟵𝟳) Although the offshore industry lacks standardized guidelines, this article identifies some criteria that an engineer should consider in the design of offshore heating, ventilating, and air-conditioning (HVAC) systems. ▶️ 𝗕𝘂𝗶𝗹𝗱𝗶𝗻𝗴'𝘀 𝗰𝗼𝗻𝘀𝘁𝗿𝘂𝗰𝘁𝗶𝗼𝗻 Most offshore buildings are constructed of continuous seal-welded steel or stainless steel plate. These buildings provide space for living quarters, electrical-control equipment, workshops, and storage. Typically, the buildings have insulated corrugated walls and roofs. The walls and roof will have fire and blast rating such as A0, A60, H60, or even H120. ▶️𝗔𝗶𝗿 𝗗𝗶𝘀𝘁𝗿𝗶𝗯𝘂𝘁𝗶𝗼𝗻 The air distribution system should be designed to have a constant volume and low velocity. To provide zoning, the system should have electric reheat coils for individual rooms and electronic room thermostats for local control of each coil. Hood ventilation systems requiring more than 400 cfm of exhaust should have a makeup air system to provide 85% of the design exhaust. The system also should include a prefilter and preheat feature. Bathrooms and clothes dryers also require dedicated exhaust systems. ▶️𝗣𝗿𝗲𝘀𝘀𝘂𝗿𝗶𝘇𝗮𝘁𝗶𝗼𝗻, 𝘀𝗮𝗳𝗲 𝗮𝗶𝗿 Outside air or safe air is an important criterion in the design of HVAC systems because most offshore buildings are pressurized or slightly pressurized. Typically, the final safe-air requirement will equal the sum of the amount of pressurization and the amount of building exhaust air, such as toilet exhaust, galley exhaust, and battery room exhaust. ▶️𝗛𝗩𝗔𝗖 𝗲𝗾𝘂𝗶𝗽𝗺𝗲𝗻𝘁 Because of the salt laden, marine environment, offshore HVAC units usually have a stainless steel (316L) or coated steel housing. Many HVAC system manufacturers have proprietary coating systems; however, not all coatings are the same or long lasting. Most coatings are enhanced epoxy or polyurethane paint systems. ▶️𝗗𝘂𝗰𝘁 𝘀𝘆𝘀𝘁𝗲𝗺𝘀 All sheet metal construction should follow the SMACNA velocity and duct construction standards, unless otherwise required by the operating company. Interior sheet-metal duct material should include with galvanizing of not less than ASTM A525 G90 (11/4 oz/sq ft), and with name of manufacturer and trade name stamped on each sheet. ▶️𝗙𝗶𝗿𝗲 𝗽𝗿𝗼𝘁𝗲𝗰𝘁𝗶𝗼𝗻 Other than the normal fire protection and detection systems for the building itself, the design requires duct-mounted smoke detectors, as per NFPA requirement, to shut down the HVAC system upon sensing smoke in the duct systems. ▶️𝗘𝗹𝗲𝗰𝘁𝗿𝗶𝗰𝗮𝗹, 𝗶𝗻𝘀𝘁𝗿𝘂𝗺𝗲𝗻𝘁𝗮𝘁𝗶𝗼𝗻 NEC requirements state that each HVAC unit should have a local disconnect switch. Even though most of the buildings usually are in a nonclassified area, it is always a good practice to rate all exterior HVAC equipment to be suitable for operating in Class 1, Division 2 areas.
To view or add a comment, sign in
-
🚀 𝗛𝗩𝗔𝗖 𝗳𝗼𝗿 𝗢𝗶𝗹 & 𝗚𝗮𝘀 𝗙𝗮𝗰𝗶𝗹𝗶𝘁𝗶𝗲𝘀 ( 𝗦𝗲𝗿𝗶𝗲𝘀- 𝟱𝟳 | 𝗣𝗮𝗿𝘁 𝟭𝟲 𝗼𝗳 𝟵𝟳) Although the offshore industry lacks standardized guidelines, this article identifies some criteria that an engineer should consider in the design of offshore heating, ventilating, and air-conditioning (HVAC) systems. ▶️ 𝗕𝘂𝗶𝗹𝗱𝗶𝗻𝗴'𝘀 𝗰𝗼𝗻𝘀𝘁𝗿𝘂𝗰𝘁𝗶𝗼𝗻 Most offshore buildings are constructed of continuous seal-welded steel or stainless steel plate. These buildings provide space for living quarters, electrical-control equipment, workshops, and storage. Typically, the buildings have insulated corrugated walls and roofs. The walls and roof will have fire and blast rating such as A0, A60, H60, or even H120. ▶️𝗔𝗶𝗿 𝗗𝗶𝘀𝘁𝗿𝗶𝗯𝘂𝘁𝗶𝗼𝗻 The air distribution system should be designed to have a constant volume and low velocity. To provide zoning, the system should have electric reheat coils for individual rooms and electronic room thermostats for local control of each coil. Hood ventilation systems requiring more than 400 cfm of exhaust should have a makeup air system to provide 85% of the design exhaust. The system also should include a prefilter and preheat feature. Bathrooms and clothes dryers also require dedicated exhaust systems. ▶️𝗣𝗿𝗲𝘀𝘀𝘂𝗿𝗶𝘇𝗮𝘁𝗶𝗼𝗻, 𝘀𝗮𝗳𝗲 𝗮𝗶𝗿 Outside air or safe air is an important criterion in the design of HVAC systems because most offshore buildings are pressurized or slightly pressurized. Typically, the final safe-air requirement will equal the sum of the amount of pressurization and the amount of building exhaust air, such as toilet exhaust, galley exhaust, and battery room exhaust. ▶️𝗛𝗩𝗔𝗖 𝗲𝗾𝘂𝗶𝗽𝗺𝗲𝗻𝘁 Because of the salt laden, marine environment, offshore HVAC units usually have a stainless steel (316L) or coated steel housing. Many HVAC system manufacturers have proprietary coating systems; however, not all coatings are the same or long lasting. Most coatings are enhanced epoxy or polyurethane paint systems. ▶️𝗗𝘂𝗰𝘁 𝘀𝘆𝘀𝘁𝗲𝗺𝘀 All sheet metal construction should follow the SMACNA velocity and duct construction standards, unless otherwise required by the operating company. Interior sheet-metal duct material should include with galvanizing of not less than ASTM A525 G90 (11/4 oz/sq ft), and with name of manufacturer and trade name stamped on each sheet. ▶️𝗙𝗶𝗿𝗲 𝗽𝗿𝗼𝘁𝗲𝗰𝘁𝗶𝗼𝗻 Other than the normal fire protection and detection systems for the building itself, the design requires duct-mounted smoke detectors, as per NFPA requirement, to shut down the HVAC system upon sensing smoke in the duct systems. ▶️𝗘𝗹𝗲𝗰𝘁𝗿𝗶𝗰𝗮𝗹, 𝗶𝗻𝘀𝘁𝗿𝘂𝗺𝗲𝗻𝘁𝗮𝘁𝗶𝗼𝗻 NEC requirements state that each HVAC unit should have a local disconnect switch. Even though most of the buildings usually are in a nonclassified area, it is always a good practice to rate all exterior HVAC equipment to be suitable for operating in Class 1, Division 2 areas.
To view or add a comment, sign in
-
Mechanical systems designs for the Villa Mousa project. 1) #HVAC_System: ✅ The areas that want an air conditioning and ventilation system have been well studied and divided into different areas according to the nature and type of air conditioning system used. ✅ The loads for the areas were calculated and the appropriate air conditioning systems for each area were selected in coordination with the project owner and the architect. ✅ The air duct paths were well made and we coordinated with the architect on the nature and shape of the air terminal outlets so that we ultimately obtain a good aesthetic appearance and a modern contemporary smart design. ✅ All equipment, air terminal outlets, and air ducts are listed in tables designated for each type, indicating the type and all characteristics and properties. 2) #Firefighting_System: ✅ The building's fire-fighting system was designed based on its type of hazard and occupancy. ✅ Water network system for fire fighting..., - A water pipe network was designed to feed the fire-fighting sprinklers that were used in the building. - The network is provided with 3 FHC class II, they were distributed at the entrances to the building, taking into account the travel distance. - The network was also provided with a fire department connection. - Hydraulic calculations were made for the fire network to choose and design a suitable pump room to feed a piping network. ✅ Fire fighting with gas..., - The fire in the kitchens was fought using fire extinguisher-wet were used. - The fire in the cameras and electronic systems room was fought using carbon dioxide fire extinguishers CO2. ✅ Quantities of all equipment, sprinklers and fire extinguishers were recorded in tables scheduled. 3): #Domestic_System: ✅ The building's hot and cold water supply system was designed based on the nature of the building and the Occupancy and type of fixtures. ✅ The size of the water tanks used to store water in the event of an outage was calculated to ensure the continuity of water in the building. ✅ The central hot water feeding system was designed to feed the building and supply it with hot water, and calculations were made to choose a suitable type of central water heater. ✅ Hydraulic calculations were made for the cold and hot water supply network to choose the appropriate pumps. 3): #Drainage_System: ✅ Soil drainage network is designed, and deliver it to the nearest appropriate inspection chamber. ✅ Wast draining network is designed and delivered it to the gully trap and then to inspection chamber. ✅ Design drainage network dedicated to rainwater. ✅ Design a dedicated drainage network for water generated from air conditioners. ✅ The sizes and levels of all manholes and inspection chamber outside the building were calculated. All thanks and appreciation Eng. Ahmed Shuhayb Co. Ahmed Shehab ASEC - أسيـــك Eng.X - انجيكس #HVAC #Firefighting #Plumbing #MEP #BIM #Mousa_Villa #AutoCAD #Revit #Abo_Elsayed
To view or add a comment, sign in
-
🚀 𝗛𝗩𝗔𝗖 𝗳𝗼𝗿 𝗢𝗶𝗹 & 𝗚𝗮𝘀 𝗙𝗮𝗰𝗶𝗹𝗶𝘁𝗶𝗲𝘀 ( 𝗦𝗲𝗿𝗶𝗲𝘀- 𝟱𝟳 | 𝗣𝗮𝗿𝘁 𝟭𝟲 𝗼𝗳 𝟵𝟳) Although the offshore industry lacks standardized guidelines, this article identifies some criteria that an engineer should consider in the design of offshore heating, ventilating, and air-conditioning (HVAC) systems. ▶️ 𝗕𝘂𝗶𝗹𝗱𝗶𝗻𝗴'𝘀 𝗰𝗼𝗻𝘀𝘁𝗿𝘂𝗰𝘁𝗶𝗼𝗻 Most offshore buildings are constructed of continuous seal-welded steel or stainless steel plate. These buildings provide space for living quarters, electrical-control equipment, workshops, and storage. Typically, the buildings have insulated corrugated walls and roofs. The walls and roof will have fire and blast rating such as A0, A60, H60, or even H120. ▶️𝗔𝗶𝗿 𝗗𝗶𝘀𝘁𝗿𝗶𝗯𝘂𝘁𝗶𝗼𝗻 The air distribution system should be designed to have a constant volume and low velocity. To provide zoning, the system should have electric reheat coils for individual rooms and electronic room thermostats for local control of each coil. Hood ventilation systems requiring more than 400 cfm of exhaust should have a makeup air system to provide 85% of the design exhaust. The system also should include a prefilter and preheat feature. Bathrooms and clothes dryers also require dedicated exhaust systems. ▶️𝗣𝗿𝗲𝘀𝘀𝘂𝗿𝗶𝘇𝗮𝘁𝗶𝗼𝗻, 𝘀𝗮𝗳𝗲 𝗮𝗶𝗿 Outside air or safe air is an important criterion in the design of HVAC systems because most offshore buildings are pressurized or slightly pressurized. Typically, the final safe-air requirement will equal the sum of the amount of pressurization and the amount of building exhaust air, such as toilet exhaust, galley exhaust, and battery room exhaust. ▶️𝗛𝗩𝗔𝗖 𝗲𝗾𝘂𝗶𝗽𝗺𝗲𝗻𝘁 Because of the salt laden, marine environment, offshore HVAC units usually have a stainless steel (316L) or coated steel housing. Many HVAC system manufacturers have proprietary coating systems; however, not all coatings are the same or long lasting. Most coatings are enhanced epoxy or polyurethane paint systems. ▶️𝗗𝘂𝗰𝘁 𝘀𝘆𝘀𝘁𝗲𝗺𝘀 All sheet metal construction should follow the SMACNA velocity and duct construction standards, unless otherwise required by the operating company. Interior sheet-metal duct material should include with galvanizing of not less than ASTM A525 G90 (11/4 oz/sq ft), and with name of manufacturer and trade name stamped on each sheet. ▶️𝗙𝗶𝗿𝗲 𝗽𝗿𝗼𝘁𝗲𝗰𝘁𝗶𝗼𝗻 Other than the normal fire protection and detection systems for the building itself, the design requires duct-mounted smoke detectors, as per NFPA requirement, to shut down the HVAC system upon sensing smoke in the duct systems. ▶️𝗘𝗹𝗲𝗰𝘁𝗿𝗶𝗰𝗮𝗹, 𝗶𝗻𝘀𝘁𝗿𝘂𝗺𝗲𝗻𝘁𝗮𝘁𝗶𝗼𝗻 NEC requirements state that each HVAC unit should have a local disconnect switch. Even though most of the buildings usually are in a nonclassified area, it is always a good practice to rate all exterior HVAC equipment to be suitable for operating in Class 1, Division 2 areas.
To view or add a comment, sign in
-
How to specify a quality thermal envelope in Australia: Background: As you know, currently in Australia, the installation of insulation and building sealing is completely self-managed by builders and not at all required to be verified by any authority! No surprise there is very very likely a huge performance gap between energy rating and actual built results! There is room for improvement. Architects can avoid this pitfall by improving the process: oblige the builder (i.e. write into specification or special condition in contract) to undertake the `As-built verification` (ABV) assessment developed by Sustainability Victoria. The ABV on-site assessment is made up of 2 components: 1. Insulation integrity inspection. 2. Blower door test. Note that the ABV assessment process relies on EXISTING standards and test methods including thermography and blower door testing as set out in AS/NZS ISO 9972:2015 ‘Thermal performance of buildings – Determination of air permeability of buildings – Fan pressurization method’. So, builders *should* be familiar with them already. During the design stage, architects are guided by handy ABV checklists. They will help you nominate appropriate components. Find more info here: https://lnkd.in/gnTr9btJ If you want to notch up a bit: sign up a Passivhaus professional early in the design process and commit to Passivhaus Certification, which will ensure a high performance thermal envelope in even greater details (bridge-free design, condensation risk mitigation, high performance fenestration) and holistically gives you a super-comfortable home, low energy bills and a healthy indoor air quality.
To view or add a comment, sign in
-
Monitoring Water Consumption and Leaks What is RECOMMENDATIONS? Note that for single-family homes with only one water supply to the home, the inspector will attach a pressure gauge to an outside faucet, take a reading and then shut off the municipal water supply to the house. After several minutes, the inspector will determine if the pressure has dropped. A loss of pressure indicates an unseen leak. For homes with more than one water supply or without an outdoor faucet, inspectors will attach a pressure gauge to the cold water faucet for the washing machine hookup or other cold water faucet and take the pressure reading. Conducting a pressure- loss test on dwelling units in multifamily buildings will vary based on the plumbing system design. Dwelling units that are supplied through a single line with a shut-off can be tested at any point of use. The pressure loss test can most easily be done here at a washer hookup or at any fixture using an adapter. For buildings that use riser pipe layouts, the test is simplest at the whole building level. As a first step, when designing the plumbing system for a multifamily building, consider supplying each unit with a single pipe source and stubbing out for a meter to facilitate individual unit submetering. This will reduce costs associated with having to install multiple meters/monitors for several points of use attached to a single riser pipe. When selecting equipment that is best suited for accurately measuring water use in each unit, note that water use within individual units will fluctuate between low and peak flows depending on the unit’s occupancy and the time of day. We recommend positive displacement meters, but consult with the meter or monitor manufacturer to select an appropriately sized device for the application. The building’s and the individual units’ size, function, fixture types, usage, occupancy, and peak population will influence minimum and maximum flow rates and proper sizing. Note that improper installation can lead to metering/monitoring inaccuracies. In general, we recommend installing meters and/or monitors in an accessible location to allow for reading and repair and in a location protected from potential damage. To ensure uniform flow entering and exiting the meter or monitor, we recommend locating the monitoring device where there is sufficient length of straight pipe before and after the device. Consider installing a strainer to prevent debris and sediment from entering the meter/monitor and causing reading inaccuracies.
To view or add a comment, sign in
-